Content :
2 zones conventional fire alarm control panel Master panel
1.1 Product Features
The panels have the following key features:
2 conventional input zones.
1 notification appliance circuits (NAC) with built-in synchronization for ANSI 3.41and Gentex.
The panel comes with a 2 amp power supply.
Dedicated alarm and trouble relays.
1 RS485 can be able to connect the other panel.
Housed in a 205mm W * 258mm H * 81mm D metal enclosure.
Enclosure supports two 12V, 4Ah backup batteries.
The panel can be used independently or connect by RS485.
1.2 Electrical Specifications
Primary AC 120VAC 50/60 Hz Power supply rating
240VAC 50/60 Hz
Power supply rating 2 Amps 24VDC
Maximum Battery Charging Current 0.98 Amps 26VDC
Initiating Device Circuits 2 Zones Alarm Zone 2
Normal Initiating Operating Voltage 23VDC, Maximum 26VDC, regulated
Normal Quiescent Current (normal status)